V1.00, August 30, 2004TTC-10003 Probe Transformer Temperature ControllerInstruction & Operation Manual 215 State Route 10, Building 2Randolph, NJ
V1.00, August 30, 20042• Cooling system performance monitor to alarm when cooling is commandedbut the current draw of the cooling fans or pumps is ou
V1.00, August 30, 2004924. Select from the Use receiving protocol list box Xmodem protocol. If thefolder listed is incorrect, click Browse to select
V1.00, August 30, 2004936. Uploading will begin. There will be two retries. Click Cancel if more than 3retries are attempted:7. At the conclusion of
V1.00, August 30, 2004949.1.2 Upload Settings Using ProcommThe procedure to upload a setting file is as follows:1. Press Enter to display the Main M
V1.00, August 30, 2004952. Click on Data. Click on Receive File:
V1.00, August 30, 2004963. Select a folder and Type the file name. Click Save:
V1.00, August 30, 2004974. The file transfer window will open indicating progress. 128 will be recorded inByte count if successful:5. At the conclus
V1.00, August 30, 2004989.2 Download Setting FilesDownload settings transfers the binary setting file on your PC to the TTC-1000connected through the
V1.00, August 30, 2004992. Click Transfer then click Send File:3. Select the Folder by clicking Browse to locate folder where the file is to bestore
V1.00, August 30, 20041004. The following screen will show the download progress:5. If successful, the following screen will display:NOTE: Download
V1.00, August 30, 20041019.2.2 Download Settings Using ProcommCheck settings to insure Xmodem protocol is selected. To download a setting file:1. Pr
V1.00, August 30, 200432 PRODUCT DESCRIPTIONThe following section describes the front panel display, indicators, and switches,connection points, mount
V1.00, August 30, 20041022. Click Data and click Send File:3. Select Folder, type file name and click Open:
V1.00, August 30, 20041034. Progress will be indicated:5. The following screen will be displayed when complete:
V1.00, August 30, 2004104NOTE: The TTC-1000 will suspend all measurements and calculations oncedownloading is selected. The outputs will also be block
V1.00, August 30, 200410510 DATA LOGGINGData logging permits storage of time stamped temperature and load data. Theuser has the ability to change the
V1.00, August 30, 2004106There is one limitation, in the event that power is interrupted, the time stamp isstored as a data record. Time stamp records
V1.00, August 30, 200410710.4 Selecting Data PointsAny or all of the data points can be selected for logging. Change the number ofpoints or the points
V1.00, August 30, 2004108Enter:109/1)This will add P2 to the log. Type 0 to remove from the log.10.4.3 Add or Delete P3 From LogTo change this setting
V1.00, August 30, 200410910.4.5 Add or Delete Load From LogTo change this setting, enter PROGRAM mode from the front panel as discussedin Section 4.1.
V1.00, August 30, 200411010.5 Retrieving Data LogThe data log can be downloaded to a PC through the RS-232 interface.Downloading the data log does not
V1.00, August 30, 2004111END OF REPORT. STOP TEXT CAPTURE & PRESS 'Enter'The first line is the header for the data reported. The last ch
V1.00, August 30, 20044UP arrow button for navigating forward into menu categories andincreasing settings.DOWN arrow button for navigating backward in
V1.00, August 30, 20041123. Click on Capture Text. A window will open to select the Folder where the textfile is to be stored:4. Click Browse to fin
V1.00, August 30, 20041135. Press enter after the 6 in the Main Menu:6. Click on Transfer, Capture Text and click Stop to halt the data capture:
V1.00, August 30, 200411410.5.2 Saving the Data Log as a Text File Using ProComm1. Press 6 on the Enter line of the Main Menu and press the Enter key
V1.00, August 30, 20041152. Highlight the data from the screen to be stored as a text file:
V1.00, August 30, 20041163. Select the Path and file name for the text file. Click Save:
V1.00, August 30, 200411710.6 Import to ExcelThe text file captured can be imported into excel for plotting and sorting. It is agood idea to open the
V1.00, August 30, 20041182. Go to the Path where the text file is stored and select Files of Type: TextFiles, Double Click the file name and Click Op
V1.00, August 30, 20041194. Check the Comma box in Delimiters. Make sure all other boxes areunchecked:5. Click the General button in the Column data
V1.00, August 30, 20041206. After closing the import wizard, the text data will display:The data is now ready for graphing.
V1.00, August 30, 200412111 DOWNLOAD PROGRAM UPDATESThe TTC-1000 firmware contains a boot loader that allows the user to downloadnew firmware. Downlo
V1.00, August 30, 200452.2 Connection OverviewThe Figure 2.2 describes the available connections.Figure 2.2: Connection OverviewTTC-1000-XXX1021342345
V1.00, August 30, 2004122The user has approximately 90 seconds to find the file and start the downloadprocess. The user will see the following message
V1.00, August 30, 20041232. Find the Path and file name. 90 seconds are allotted to find the file:3. Select Xmodem from the Protocol pull down list.
V1.00, August 30, 20041244. Click on the file name and click open. Click Send:5. The download will now begin. Clicking Cancel aborts the transfer:
V1.00, August 30, 20041256. If the transfer is successful, the following screen will be displayed to wait 15seconds for the transfer to be “burned-in
V1.00, August 30, 200412611.2 Download Firmware Using ProcommMake sure the Transfer Protocol is set for XMODEM. To download firmwareusing Procomm:1.
V1.00, August 30, 20041272. Find the folder containing the file to be transferred.
V1.00, August 30, 20041283. Click Open:
V1.00, August 30, 20041294. The download will now begin. Clicking Cancel aborts the transfer:
V1.00, August 30, 20041305. If the transfer is successful, the following screen will be displayed to wait 15seconds for the transfer to be “burned-in
V1.00, August 30, 20041316. Press the Enter key after 15 seconds to display the Main Menu:7. If the Main Menu does not appear, check the front panel
V1.00, August 30, 200462.3 SpecificationsPower Supply Input Operating Range:38 VDC to 160 VDC or 120VAC ±10%, 3 Watts maxOperating Temperature Range:-
V1.00, August 30, 200413212 SETTINGS WORKSHEETSThe following worksheet is a comprehensive list of all the settings programmablethrough the RS-232 inte
V1.00, August 30, 200413312.1 Front Panel Setting SheetsSetting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to001 SP11PICKUP Probe #
V1.00, August 30, 2004134Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to016 SP24DRPOUT Probe #2 dropouttemperature0 to 160 °C
V1.00, August 30, 2004135Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to029 DIRECTED FOA(functional only inunits equipped wit
V1.00, August 30, 2004136Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to041 LTCDIFF2 DO (Notfunctional in singleprobe units)L
V1.00, August 30, 2004137Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to050 IN1=LEVEL orPULSE(functional only inunits equippe
V1.00, August 30, 2004138Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to057 (!) SP12 (*/+) TOOUTnAssigns probe #1 setpoint t
V1.00, August 30, 2004139Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to062 (!) SP23 (*/+) TOOUTn(Not functional insingle pr
V1.00, August 30, 2004140Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to067 (!) SP34 (*/+) TOOUTn(Not functional insingle pr
V1.00, August 30, 2004141Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to072 (!) WSP3 (*/+) TOOUTn(functional only inunits eq
V1.00, August 30, 20047NEMA 4X: 10” H x 6” W x 3.25” D. 304 Stainless SteelSurge Withstand/Fast Transient:Relay outputs, and station battery inputs: A
V1.00, August 30, 2004142Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to077 (!) IN2 (*/+) TOOUTn(functional only inunits equi
V1.00, August 30, 2004143Setting # Setting Purpose Setting Range or Values FactoryDefaultProgram to082 TIMESETPOINT100:00-00:00 >OUT0,1,2,3,4OR&apo
V1.00, August 30, 2004144Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to092 P3 NAME Probe #3 name(optional)TOP OIL, WINDING,A
V1.00, August 30, 2004145Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to105 TIME Sets military time HH:MM 00:00106 MONTH Sets
V1.00, August 30, 2004146Setting # Setting Purpose Setting Range orValuesFactoryDefaultProgram to115 OUT3(Action)w/ALRMAction: UNCHG,PCKUP,SUPVAllows
V1.00, August 30, 200414712.2 PC Setting SheetsSetting # Setting Purpose Setting Range or Values Program to01SP11 PICKUP Probe #1 set point#1 pickupte
V1.00, August 30, 2004148Setting # Setting Purpose Setting Range or Values Program to10 SP21 DRPOUT Probe #2 set point#1 dropouttemperature10/nnnwhere
V1.00, August 30, 2004149Setting # Setting Purpose Setting Range or Values Program to18 SP31 DRPOUT Probe #3 set point#1 dropouttemperature18/nnnwhere
V1.00, August 30, 2004150Setting # Setting Purpose Setting Range or Values Program to25 WSP1 PICKUP Calculated windingpickup temperature25/nnnwhere nn
V1.00, August 30, 2004151Setting # Setting Purpose Setting Range or Values Program to34 LTCDIFF1DRPOUTLTC Differential 1drop outtemperature34/-nn or 3
V1.00, August 30, 200482.4 Part Number DetailsNOTE: Consult the factory for other options not listed.TTC- PROBE- 0 t -zzzProbe lead length, zzz=10 to
V1.00, August 30, 2004152Setting # Setting Purpose Setting Range or Values Program to42 LSP2 DRPOUT Load dropoutcurrent42/n.nwhere n.n=0.0 to 9.9SET O
V1.00, August 30, 2004153Setting # Setting Purpose Setting Range or Values Program to51 OUT2AUTO/MANUALOperate Output inAUTO or MANUALcontrol51/0: AUT
V1.00, August 30, 2004154Setting # Setting Purpose Setting Range or Values Program to59 (!) SP11 (*/+)TO OUTnProgrammable logicfor SP1159/0/0/0: SP11
V1.00, August 30, 2004155Setting # Setting Purpose Setting Range or Values Program to63 (!) SP21 (*/+) TOOUTnProgrammable logic forSP21DO NOT USE FOR
V1.00, August 30, 2004156Setting # Setting Purpose Setting Range or Values Program to67 (!) SP31 (*/+) TOOUTnProgrammable logic forSP31DO NOT USE FOR
V1.00, August 30, 2004157Setting # Setting Purpose Setting Range or Values Program to71 (!) LTCDIFF1(*/+) TO OUTnProgrammablelogic for LTCDIFF1DO NOT
V1.00, August 30, 2004158Setting # Setting Purpose Setting Range or Values Program to75 (!) WSP3 (*/+)TO OUTnProgrammablelogic for WSP3SET ONLY IF Aux
V1.00, August 30, 2004159Setting # Setting Purpose Setting Range or Values Program to79 (!) OUT1 (*/+)TO OUTnProgrammablelogic for OUT179/0/0/0: OUT1
V1.00, August 30, 2004160Setting # Setting Purpose Setting Range or Values Program to83 (!) IN1 (*/+) TOOUTnProgrammablelogic for IN1SET ONLY IFOptic
V1.00, August 30, 2004161Setting # Setting Purpose Setting Range or Values Program to89 OUT2 INVERT Inverts OUT2 89/0: Not INVERT89/1: INVERT90 OUT3 I
V1.00, August 30, 200493 INSTALLATION and CONNECTIONSThe following section gives information on hookup of power, temperature probes,split core CT, ou
V1.00, August 30, 2004162Setting # Setting Purpose Setting Range or Values Program to98 TPROBE2 NAME Names PROBE2 98/0: TOP OIL98/1: WINDING98/2: AMBI
V1.00, August 30, 2004163Setting # Setting Purpose Setting Range or Values Program to104 BAUD RATE Sets baud rate forRS-485 interface104/0: 1200 baud1
V1.00, August 30, 2004164Setting # Setting Purpose Setting Range or Values Program to115 WNDCKT ALRM Enables or disableswinding circuitalarm115/0: Ena
V1.00, August 30, 200416513 DNP3.0 PROFILE DOCUMENTDNP V3.00DEVICE PROFILE DOCUMENTVendor Name: Advanced Power Technologies, LLCDevice Name: TTC-10
V1.00, August 30, 2004166DNP V3.00DEVICE PROFILE DOCUMENTRequires Application Layer Confirmation:$ Never" Always" When reporting Event Data&
V1.00, August 30, 2004167DNP V3.00DEVICE PROFILE DOCUMENTReports Binary Input Change Eventswhen no specific variation requested:# Never" Only tim
V1.00, August 30, 2004168DNP V3.00DEVICE PROFILE DOCUMENTSequential File Transfer Support:Append File Mode " Yes # NoCustom Status Code Strings &
V1.00, August 30, 2004169TTC-1000 Data MapIndex # DNP ObjectGroup,VariationDescription00 01,02 State of Set Point SP11 (Probe 1, Set Point 1), 0-Dropp
V1.00, August 30, 200410Figure 3.2 shows the outline of the NEMA 4X enclosure. A mounting bracket,P/N:80001000126, suitable for retrofit or new applic
V1.00, August 30, 2004113.2 Power HookupThe TTC-1000 can be powered from either DC substation battery betweenvoltages of 38 to 160 VDC or from AC volt
Table of ContentsV1.00, August 30, 2004i1 INTRODUCTION...12 PR
V1.00, August 30, 200412thermometer well adapter fittings: 7/8-UNF (ANSI/IEEE C57 thermometer well),½-NPT and ¾-NPT and three probe sleeves: 0.481, 0.
V1.00, August 30, 2004135. Close the elbow, forming a 90 degree right angle. Tighten the domedstrain relief until the insert is tight against the pro
V1.00, August 30, 200414• RTV silicone sealant suitable for the outdoor applications and rated for themaximum operating temperature.• Thermal grease
V1.00, August 30, 200415Figure 3.8: Magnetic Mount, Side View3. Place a bead of RTV silicone or other suitable sealing compound around theperimeter o
V1.00, August 30, 200416Figure 3.9: Magnetic Mount, Application of RTV3.3.4 Probe Lead ConnectionsThe probe leads are color-coded and are inserted in
V1.00, August 30, 200417The resistance from the white to black probe leads is 1000 ohms and from whiteto red leads is 1000 ohms at 23° C and increases
V1.00, August 30, 200418Figure 3.11: Temperature Probe Shield Grounding3.4 Auxiliary CT Input for Calculated Winding TemperatureModels TTC-1000-xx3x
V1.00, August 30, 20041912Power34Aux CTTB11234PowerAux CTTB3TB2a) Panel Mountb) NEMA 4Figure 3.13: Auxiliary CT Connections WARNING: SEVERE DAMAGE WIL
V1.00, August 30, 200420NOCNCOUT1OUT2NC C NONC C NONC C NOOUT3OUT4TB1OUT1OUT2OUT3OUT4SHIELDTB3a) Panel Mountb) NEMA 4Figure 3.14: Connections to Relay
V1.00, August 30, 200421PROBE #1TB2COMTMPREFPROBE #2COMTMPREFALARM123456789101112AlarmREFTNFCOMREFTMPCOMTB2a) Panel Mount b) NEMA 4the unit to provide
Table of ContentsV1.00, August 30, 2004ii4.3.5 Calculated Winding Exponent Setting...324.3.6 Checking Wind
V1.00, August 30, 200422PIN FUNCTION1 No connection2 Receive Data3 Transmit Data4 No connection5 Ground6 No connection7 Request to send8 Clear to send
V1.00, August 30, 200423Figure 3.18: Location of J2 RS-485 Bus Termination JumperNOTE: For panel mount versions, the unit contains the jumper but it i
V1.00, August 30, 200424Figure 3.19: Panel Mount and NEMA 4 RS-485 ConnectionsFigure 3.20: Four Wire RS-485 ConnectionsThere are many good references
V1.00, August 30, 200425and IN2 can be programmed to be LEVEL or PULSE active. Figure 3.21illustrates these connections. The use of shielded cable is
V1.00, August 30, 2004264 SETTINGSSettings can be made either through the front panel or using a PC equipped withterminal emulation software. Proper o
V1.00, August 30, 200427emulation be set for either ANSI or TTY. The pin out of this port is designed touse a 9 pin female to 9 pin male null modem ca
V1.00, August 30, 20042851 OUT2 AUTO (0)52 OUT2 SUPVS (2) w/ALRM53 OUT3 PICKUP TMR=00 sec54 OUT3 AUTO (0)55 OUT3 UNCHG (0) w/ALRM56 OUT4 PICKUP TMR=00
V1.00, August 30, 200429115 WNDCKT ALRM ENABLED (0)116 DEVICE ALRM ENABLED (0)117 TEMPERATURE ALRM ENABLED (0)118 MANUAL ALRM ENABLED (0)119 TIME SP C
V1.00, August 30, 200430TTopOil = Measured Top Oil temperatureIt is noted that the Hot Spot Rise over Top Oil at rated load is not alwaysavailable. In
V1.00, August 30, 2004314.3.2 Rated LoadThe Rated Load setting is the top name plate rating in Amps. If the nameplateindicates ratings of 1000/1200/14
Table of ContentsV1.00, August 30, 2004iii4.13.4Winding Circuit Alarm Setting ...694.14 Settin
V1.00, August 30, 200432Enter:94/20) This will program the hot spot rise to 20 degrees Celsius.4.3.4 Winding Rise Time ConstantThe Winding Rise Tim
V1.00, August 30, 200433Enter:80/1)This will program the Cooling Type to directed FOA/FOW. Enter 0 for all othercooling types.4.3.6 Checking Winding T
V1.00, August 30, 200434• AMBIENT• LTCDIFF• BOTMOIL• TOPOIL1• TOPOIL2• TOPOIL3• LTCDIF1• LTCDIF2NOTE: The MIN/MAX log should always be reset after cha
V1.00, August 30, 2004355... TOPOIL16... TOPOIL27... TOPOIL38... LTCDIF19... LTCDIF2Therefore to display TOPOIL for probe 1 type:Enter:
V1.00, August 30, 200436Figure 4.1: Over Temperature OperationSPpn Pick UpTemperatureSPpn Drop OutTemperatureTemperatureTimeSPpn
V1.00, August 30, 200437Figure 4.2: Under Temp OperationOnce a set point has picked up, it will not drop out until the pre-programmedconditions are me
V1.00, August 30, 2004381. When changing pickup or drop out temperature set points, the newvalue takes effect the next time temperature data is updat
V1.00, August 30, 200439The remaining liquid set points can be changed by pressing the %%%% arrow buttonand following the above procedure.For programm
V1.00, August 30, 200440For programming from a PC just type the desired temperature on the “Enter:” lineas follows:Enter:25/85)This will program WSP1
V1.00, August 30, 200441The TTC-1000 uses an LTC pickup timer settable from zero to 999 minutes tosupervise the LTC set point. The above example shows
Table of ContentsV1.00, August 30, 2004iv9.2.2 Download Settings Using Procomm...10110 DATA LOGGING ...
42V1.00, August 30, 2004NOTE:1. In single probe versions, the LTCDIFF pickup and dropout settingsdisplay “N/A”.2. Be careful to check that the LTCDI
V1.00, August 30, 2004434.6.2 Setting LTCDIFF Pickup TimerProgramming LTCDIFF1 and LTCDIFF2 pick up timers from the front panel,press the %%%% or &am
V1.00, August 30, 200444Figure 4.4: Load Pickup Set Point OperationThe first case shows that the load current remains above the pickup set point forth
V1.00, August 30, 2004454.7.1 Setting Load Pickup Set PointThese settings are used to start a stage of cooling based on a sudden increasein load curr
V1.00, August 30, 2004464.7.2 Setting Load Pickup TimerProgramming Load Pickup Timer from the front panel, press the %%%% or &&&&arro
V1.00, August 30, 200447DebounceTimerINnSignalApplied toInput nDebounceTimerINnSignalApplied toInput nFigure 4.5: Input Set for LEVELFigure 4.6: Input
V1.00, August 30, 200448For programming from a PC just type the input detection, IN1 or IN2 CNTRL,mode on the “Enter:” line as follows:Enter:45/1)This
V1.00, August 30, 200449Assigning SP11 ! to OUT3 and SP21 ! and SP12 + to OUT3 will result in thefollowing Boolean expression:OUT3 = SP12 ! SP11!SP21N
V1.00, August 30, 200450NOTE: DO NOT ASSIGN SP21, SP22, SP23, SP24, or SP31,SP32,SP33,SP34IF ASSIGNING THE LTCDIFF SET POINT.To assign a liquid set po
V1.00, August 30, 200451For programming from a PC just type the SP11 assignment on the “Enter:” lineas follows:Enter:59/0/1/1)This will assign SP11 Or
Table of FiguresV1.00, August 30, 2004vFigure 2. 1a: Front Panel, Panel Mount Version...3Figure 2.1b:
V1.00, August 30, 200452Use the '''' or ((((buttons to scroll to the output #. The output number will flash.Use the %%%% or &&
V1.00, August 30, 200453Use the '''' or ((((buttons to scroll to the AND/OR logic operator. The operator willflash. Use the %%%% o
V1.00, August 30, 2004544.9.4 Assigning Load Pickup Set PointsLoad pickup set points must be assigned to a specific output to start a stage ofcooling
V1.00, August 30, 200455LSP2 can be assigned by pressing the %%%% arrow button and following the aboveprocedure.For programming from a PC just type th
V1.00, August 30, 200456Use the '''' or ((((buttons to scroll to the output #. The output number will flash.Use the %%%% or &&
V1.00, August 30, 200457The first character is the inversion operator. Use the %%%% or &&&&arrow buttons to scrollbetween the inversio
V1.00, August 30, 2004584.9.7 Time Set PointsThe time set points allow the user additional flexibility to activate events betweenspecific times. There
V1.00, August 30, 200459The following shows TSP1 set to pickup output 1 at 14:00 and drop out output 1after 14:15:TSP2 and TSP3 are set using the same
V1.00, August 30, 2004604.9.8 Setting Output TimersSetting the output timers delays the pickup of the output by the number ofseconds set. Each output
V1.00, August 30, 200461Press the YES button. The first character will flash. Use the %%%% or &&&&arrow buttonsto scroll between OFF a
Table of FiguresV1.00, August 30, 2004vi
V1.00, August 30, 200462NOTE: Do not use the inversion operator on individual set points whenremote control through DNP3.0 and fail-safe cooling contr
V1.00, August 30, 200463Use the INVERT OUTn setting to cause the output relay to drop out when eithertemperature set point is achieved. The resulting
V1.00, August 30, 2004644.10 Setting Output Control With AlarmThe TTC-1000 monitors two critical conditions: processor (DEVICE) andtemperature (TPROBE
V1.00, August 30, 200465Press the YES button. The first character will flash. Use the %%%% or &&&&arrow buttonsto scroll between PCKUP
V1.00, August 30, 200466Programming from the front panel, press the %%%%or &&&&arrow button until the setting089 is displayed:Press th
V1.00, August 30, 200467Once in Manual Mode any output relay will be de-energized if power is removedupon re-energization. The output remains in Manua
V1.00, August 30, 2004684.13.1 Device Alarm SettingA DEVICE alarm occurs anytime the microprocessor detects a failure in any ofthe peripheral hardware
V1.00, August 30, 200469Press YES when you have made the correct selection. Selecting DSABL willblock the device alarm relay and the front panel alarm
V1.00, August 30, 200470–XX4X. This alarm is for reporting only and does not supervise any of the controlfunctions.Setting from the front panel, press
V1.00, August 30, 2004714.14.1 Setting Time and Date Via the Front PanelSetting from the front panel, press the %%%%or &&&&arrow butto
WarrantyV1.00, August 30, 2004viiAll new products sold to customers are warranted against defects in design, materials, and workmanship forthe life of
V1.00, August 30, 200472Press the YES button. The 10’s year digit will flash. Use the %%%% or &&&&arrow buttonsto set this digit. Use
V1.00, August 30, 200473It is important to remember to enter the password as a four digit number. Failureto enter a four digit number will result in a
V1.00, August 30, 2004745 TELEMETRY OPTIONSThis section will discuss the various telemetry options available, their use andany relevant settings. The
V1.00, August 30, 200475data if available. Also, the TTC-1000 uses two points to identify whether or notthe probe is measuring Top Oil, Heated Well, L
V1.00, August 30, 200476implementation is that the top priority of the Main microprocessor is for controland monitoring and the Communications Process
V1.00, August 30, 200477To change this setting, enter PROGRAM mode from the front panel as discussedin Section 4.1. To set the node address from the f
V1.00, August 30, 200478For programming from a PC, enter PROGRAM through the main menu asdiscussed in Section 4.2. Once in PROGRAM, type the setting f
V1.00, August 30, 2004796 VIEW TEMPERATURESThe temperature & time display will be the first display you see upon power up.Date, time, and temperat
V1.00, August 30, 2004806.2 Dual ProbeFor dual probe units, model number –XX2X the display sequence will appear asfollows:The name set for P1 and P2 w
V1.00, August 30, 2004816.3 Three Probe07/29/03 13:15P1 TOPOIL1 45°CTOPOIL1 MIN= 35°C@ 03:15 07/29/03TOPOIL1 MAX= 65°C@ 17:42 07/18/03RST MIN
1V1.00, August 30, 20041 INTRODUCTIONThe TTC-1000, 3 Probe Transformer Temperature Controller is a missionspecific programmable controller that measur
V1.00, August 30, 2004826.4 Single Probe With Calculated WindingFor single probe units with calculated winding temperature, model number –XX3X the di
V1.00, August 30, 2004836.5 Dual Probe With Calculated WindingFor dual probe units with calculated winding temperature, model number –XX4Xthe display
V1.00, August 30, 2004846.6 Reset Min/MaxThe minimum and maximum registers may be reset by pressing the YES buttonwhen the display is showing:To confi
V1.00, August 30, 2004857 VIEW SETTINGSView allows display of settings without entering PROGRAM. Settings may beviewed from the front panel or via a P
V1.00, August 30, 20048633 LTCDIFF1 PICKUP=05 øC34 LTCDIFF1 DRPOUT=00 øC35 LTCDIFF2 PICKUP=05 øC36 LTCDIFF2 DRPOUT=00 øC37 LTCDIFF PICKUPTMR1=480 MIN
V1.00, August 30, 20048797 TPROBE1 NAME=TOPOIL1 (5)98 TPROBE2 NAME=TOPOIL2 (6)99 TPROBE3 NAME=TOPOIL3 (7)100 ALTERNATE=DSABL (0)101 ANALGOUT=N/A102 A1
V1.00, August 30, 2004888 STATUSSTATUS allows you to take a snapshot of the recognized state of any output,temperature set points, LOAD, LTCDIFF set p
V1.00, August 30, 200489WSP4=PICKED UPLSP1=PICKED UPLSP2=PICKED UPIN1=DRP'D OUTIN2=DRP'D OUTOUT1=PICKED UPOUT2=DRP'D OUTOUT3=DRP'D
V1.00, August 30, 2004909 SETTING FILESUploading and downloading of setting files can only be accomplished throughconnection from a PC directly connec
V1.00, August 30, 2004912. After pressing 4 and Enter:3. Click on Transfer and click Receive File:
Commentaires sur ces manuels